Brands / Metered & Switched PDU / 8031
8031
Part Number: 8031

8-fold switched and metered PDU

Model Number 8031
Input Current 16 A, 110-230 V
Number of Power Ports 8
Control Interface HTTP(S), SNMP, ModbusTCP, Telnet, SSH, MQTT, RS232
Environment Monitoring 2 sensor connectors
Installation 19 inch racks, 1 HU
Brand Gude Systems

Contact for Pricing

Contact Us

Key Features

General

Event and schedule controlled switching
Precise current metering of up to 9 electrical units and residual current
2 connectors for plug-and-play sensors
Simple and quick mounting due to integrated mounting straps
NTP function can be activated
Integrated overvoltage protection type 3
Robust plastic housing

Switching Function

Each power port can be switched via HTTP(S), SNMP, ModbusTCP, Telnet, SSH, MQTT and serial interface
Programmable on/off sequences for remote reboots (Remote Reboot)
Power ports can be switched when preset sensor thresholds are exceeded
Self-healing function thanks to 8-channel watchdog (ICMP/TCP)
Switching state and switch-on delay up to 9999 seconds (166 minutes)
Sequential switch-on with a latency of 1 second prevents current peaks
Zero Voltage Switching (ZVS)

Metering Function

Power consumption metering (kWh) with 2 energy counters
Metering of current, voltage, power factor, frequency, active power, apparent power and reactive power
Metering of differential current type A (mA) and type B (mA)
2 connectors for combined plug-and-play sensors (temperature, humidity, air pressure)

Security

Integrated type 3 overvoltage protection
Long-life High-Inrush Relays prevent welding of relay contacts
Generation of status messages and alarms (e-mail, syslog, SNMP traps, MQTT, SSH, Telnet)
Encrypted e-mails (SSL, STARTTLS)
IP access control and 802.1X authentication
Encrypted communication through SSL (TLS 1.1, 1.2, 1.3) and SSH
Password protected access
Beeper for audible alarm when sensor limits are exceeded
IEC-Lock power ports prevent accidental unplugging (for 8031-2)

Operation

LED display for total current, IP address and sensor values
Firmware update via Ethernet during operation (no restart required)
Configuration via web browser, Windows or Linux program
Dynamic IP address via DHCP or static IP
Rapid commissioning with free drivers

Technical Specifications

Technical Details
Overvoltage Protection Integrated type 3 (L-N, L/N-PE), status via network
High-inrush Relay max. 4 sec: 30 A / max. 20 ms: 80 A
Zero Voltage Switching ± 0.8 ms with temperature compensation
Measurement Current (A), Voltage (V), Phase angle, Power factor, Frequency (Hz), Active power (W), Apparent power (VA), Reactive power (VAr)
Residual Current Type A (mA)
Security SSL (TLS 1.1, 1.2, 1.3), SSH
Dimensions (LxDxH) 439 x 178 x 44 mm (without mounting brackets)
Weight Approx. 2.7 kg
Operating Temperature 0-50 °C
Storage Temperature -20 – 70 °C
Relative Humidity 0 – 95 % (non condensing)
Electrical Connections
8031-1 Power Supply 1x IEC C20 (max. 16 A, 230 V)
8031-1 Power Ports 8x IEC C13 (max. 10 A each)
8031-2 Power Ports 8x IEC C13 Lock (max. 10 A each)
8031-3 Power Ports 8x Safety Socket Type F (max. 16 A)
8031-4 Power Ports 8x Type G, BS 1363 (max. 13 A)
8031-6 Power Ports 8x NEMA 5-15 (max. 12 A)
Ethernet 1x RJ45 (10/100 Mbit/s)
Serial Interface 1x RS232 (Sub-D, 9-pin)
Sensor Connectors 2x RJ45 for plug-and-play sensors
Order Codes
8031 8x IEC C13, 8x IEC C13 Lock, 8x Type F, 8x Type G, 8x NEMA
Scope of Delivery
Unit Expert Power Control 8031
Power Cable 1x power supply cable (safety socket type F – IEC C19 or UK – IEC C19), length: 2 m
Documentation Quick start guide
More Info
← Back to Metered & Switched PDU